![]() | Overview CFS10 insertion style magnetic flowmeter is used to measure the flow of conductive liquids, colloids, and suspensions in pipelines. It can output one 4-20mA analog quantity and two switching quantities. The flowmeter is installed in a plug-in type, which is convenient for installation and replacement, and has no moving parts. •Digitization, local digital display of measurement results; •Easy to maintain, disassembly and assembly can be completed without tools; •No moving parts •Bi-directional flow; •No pressure drop; •Empty pipe detection •Suitable for water media; |
Dimensional drawing | Connection & pin assignment • External loop power (24 VDC) is required. • Factory standard calibration is 4 to 20 mA = 0 to 5 m/s. • The 4 to 20 mA output can be spanned to any range, from -10 m/s to +10 m/s. • AUX PWR must be connected to power the display backlighting and to power to the relay coils if included. |
General information
Range of application Flow Rate Range (Bi-directional) Pipe Size Range Linearity Repeatability | Water 0.05... 10 m/s DN25 to DN900 (½ in. to 36 in.) ±1% of reading +0.01 ms (0.033 ft/s) ±0.5% of reading @ 25 ℃ (77 °F) |
Power Requirements
4 to 20 mA
Frequency Digital Auxiliary
Reverse polarity and short circuit protected | 21.6 to 26.4 VDC, 22.1 mA max. 400 mV p-p maximum ripple voltage 5 to 26.4 VDC, 15 mA max. 5 to 6.5 VDC, 15 mA max. 9 to 24 VDC, 0.4A max (only required for units with relays) |
Current output (4 to 20 mA)
Max Loop Resistance Loop Accuracy Temp. drift Power supply rejection Isolation Maximum cable Error condition | 300 Ω 32 μA max. error (25 ℃ @ 24 VDC) ± 1 μA per ℃ max. ± 1 μA per V Low voltage < 48 VAC/DC from electrodes and aux power 300 m (1000 ft) 22.1 mA |
Relay Specifications
Relay 1 and 2 Type Rating
Relay 3 Type Rating Hysteresis Trigger Delay Relay Modes Relay Source Error Condition | Mechanical SPDT 5 A @ 30 VDC max., 5 A @ 250 VAC max. Solid State 50 mA @ 30 VDC, 50 mA @ 42 VAC Adjustable, plus timer delay Adjustable (0 to 9999.9 sec.) Off, Low, High, Window, and Proportional Pulse Flow Rate, Resettable Totalizer Selectable; Fail Open or Fail Closed |
Display
Characters Contrast Backlighting | 2 x 16 User-set in four levels Requires external 9-24 VDC, 0.4 mA max. (only on relay versions) |
Environmental Requirements
Enclosure Case Display window Storage Temperature Relative Humidity Operating Temperature: Ambient Media Operating pressure: Maximum | NEMA 4X / IP65 (with cap installed) PBT Polyamide -20℃ to 70 ℃ (-4 °F to 158 °F) 0 to 95% (non-condensing)
-10 ℃ to 70℃ (14 °F to 158 °F) 0 ℃ to 85 ℃ (32 °F to 185 °F)
10.3 bar @ 25℃ (150 psi @ 77 °F) 1.4 bar @ 85 ℃ (20 psi @ 185 °F) |